21-3601E rev1.3 xL Simplified Installation Guide 25
11. Provision shall be made for a separate test of
detector in each safe or vault connected to a
single control unit.
12. A mechanical ringer shall give an indication
automatically to the user when only 5 minutes
operating power remains in the sounding device.
See Programming Section – Low Battery.
13. There shall be provision for testing or automatic
meter supervision over all sources of electrical
energy. If testing is used, it is to be made under
load with the sounding device operating.
14. To be installed with UL Listed high security cable
such as Beldon model 9512, 8444.
BURGLAR ALARM (BANK SAFE AND VAULT)
1. Same as local burglar alarm above except installed
with Listed, Rothenbuhler Engineering, Model 5110
Electronic Sounding Device.
2. One 17 Ah battery shall be used to provide the 72 h
standby time followed by 15 min of alarm and
extended power loss of 72 h.
BURGLAR ALARM (POLICE CONNECT) GRADE A-
DACT+BELL, HIGH LINE SECURITY (AA) – PACKET
SWITCHED DATA NETWORK
Same as local burglar alarm above. System supplies
standard line security (DACT) when used with IP
Module 650-9060 as defined in UL 365.
BURGLAR ALARM (CENTRAL STATION) GRADE C-
DACT, GRADE AA – PACKET SWITCHED DATA
NETWORK, GRADE B – DACT+ GRADE A
BELL+BELL HOUSING
Same as local burglar alarm above. The system shall
be programmed to transmit the required opening and
closing signals. The system shall be programmed to
transmit the required opening and closing signals.
BURGLAR ALARM (PRORIETARY) GRADE A -
DACT, GRADE A – PACKET SWITCHED DATA
NETWORK
Same as Central Station.
HOUSEHOLD FIRE ALARM
1. If any fire alarm circuits are present on the zone
expansion devices, the Amseco Model PAL-328N
trouble annunciating device shall be connected to
an open collector output programmed to activate if
the bus fails. The device provides supervision of
the remote fire alarm initiating circuits.
2. A Listed audible signaling device suitable for fire,
rated to operate over the range of 11.0 to 12.3 V
shall be used.
3. The maximum total current draw from auxiliary,
snapp, and outputs 1, 2, combined shall not exceed
1.0A.
4. Siren plus all other loads must never exceed 1.0 A.
5. System shall be connected to a Listed smoke
detector rated to operate over the range of 11.0 to
12.3 V dc. The last detector on the initiating circuit
shall be a Listed ESL Model 449CTE with built-in
end-of-line relay. The circuit shall also be
terminated with a Model 166-6841 end-of-line
resistor.
HOUSEHOLD BURGLAR ALARM
1. Refer to Grade A local burglar alarm above for
maximum standby and loading conditions.
2. Maximum entrance delay time shall not exceed
45s.
3. System shall employ a Listed-sounding device
rated to operate over the range of 11.0 to
12.3 V dc.
4. All zones shall be programmed to be supervised
with a 2.2 kilohm end-of-line resistor.
5. The system shall be housed in the Model 6801
enclosure.