202
MONITOR AFx™ Director V4.1 User's Guide
500-9041 v4.1
If you change any value for an elevator/lift, this will
cause that device to be reset to its default / scheduled
state (this allows configuration updates to be managed
properly). To check or re-set status aspects, refer to
the "Elevator" status/control topic.
Introducing Access-Controlled
Elevators
With access-controlled elevators, floor call-
buttons are disabled until an authorized person
presents their access card. When the card is
presented, the specific floors for that person
will become available.
Each system can include up to
32
elevators,
and a total of up to
124
access-controlled
floors.
Exception: The elevator capacity is shared with doors
(max. 32 combined). Doors also share the elevator
numbering (and panel memory space), and will be listed
along with the doors (editable under "Door" only).
Tip: You can define elevators at the end of the list, or
click
[Filter]
on the toolbar to show only the numbers
associated with elevators.
Panel/Firmware Revision:
Support for elevators and
controlled floor-access requires V3.0 panel firmware.
Recommended:
V3.2
panel firmware, and
V1.5
elevator controller firmware.
Feature-Set and Licensing: Support for elevators
requires a 'feature-set' selection of
5
or higher (via
Enterprise software licensing).
For details, refer to "Account-Wide Panel Settings", and
"Software Activation and Licensing".
Floor Wiring and Set-Up: Floor relays must be wired in
the same relative order for all elevators, and then
defined in the same order (such as lowest to highest).
To define system floors, refer to the floor configuration
topic (to follow).
The access-requirements for each elevator
reader can be configured to meet your specific
requirements. As well, many items can be set
to a rotating schedule, allowing different
parameters to be in effect after-hours.
For details on setting up the card/token format, refer to
"System Card-Access Settings".
Wiegand-output reader keypads are supported for
Card+PIN (and PIN-Only) entry modes and signalling
duress. Matrix-style keypads (i.e., that require
additional connections) are
not
supported for elevators.
Accessing the Elevator Configuration
Topic
(Multi-
Account
Systems: Click
[Account Folders]
in
the 'tree', and locate and double-click the desired
account.)
Select
Elevators
from the MyTools bar,
or
click your site/account button in the tree, open
"Configuration" (
+
), and select
Elevators
.
(Under the specific panel group and panel--if
listed in the 'tree'.)
Panel Groups and Panels: The 'tree' can be set to
show configuration topics in a single list (logical tree
view), or on a panel-by-panel basis (best for multi-panel
systems). For details, refer to "Other Desktop
Choices".
Adding an Elevator to the System
(Before adding an elevator, the applicable elevator-
controller module should be set up. For details, refer to
"Expansion Modules".)
Access "Configuration Elevators" as
described previously, and use the
Grid
/
Form
toolbar-button to select your preferred 'view'.
Forms view: Details for one door at a time;
Grid View: All defined doors in a list.
Now, click
[+]
at the bottom of the form, or
right-click the form, and select
Add New
from
the pop-up menu.
Alternative: You can also select a blank/grey item from
the list (Forms view: bottom of the window). If no grey
ones are listed (or the form is blank), click
Filter
on the
toolbar, and re-check the listing.
Now, refer to the selection-descriptions for this
portion of the elevator screen while entering
and/or selecting your desired settings.
Tip:
Start with the 'Standard' tab, and then view any
additional topics of interest.
Tip:
You can copy all settings for an elevator, and
paste them into another one: Right-click the 1
st
one (a
blank area if in 'Forms' view), and select
Copy
. Then,
select a blank/new elevator from the list, right-click
again, and select
Paste
. After 'pasting', change the
name and any settings as desired.
Note:
'Copy' and
'Paste' are also available from the
E
dit
menu.
Elevators (Lifts) and Associated Readers