MONITOR AFx™ Director V4.1 User's Guide
500-9041 v4.1
Standard
- Module:
The number (from the MODULE
screen) for the elevator controller module
associated with the elevator cab.
-Port Number:
Whether this is the 1
st
or 2
nd
elevator on the selected elevator-controller
module;
- Token Format:
The card/token format
associated with this elevator (lift) cab. Up to
two card/token formats are supported for each
panel, as defined through the System Access
screen.
"Wiegand" pertains to cards/tokens for readers with
Wiegand data-format (Wiegand, Proximity, etc.).
Similarly, "Magstripe" pertains to cards for readers
with magnetic-stripe output (magstripe, bar-code,
etc.).
For details on setting up the card/token format, refer to
"System Card-Access Settings".
- LCD Name:
A shorter version of the name to be
displayed at LCD keypads. This is assigned
automatically, and can also be changed if
desired (max. 12 chars., plain text).
Extended
- Bi-Colour LED Mode:
Select this if the reader
at this door has a single bi-colour LED (instead
of the two separate LEDs).
Note:
Arming-stations are not supported in elevator
cabs.
- Insertion Type Reader:
Ensures the access
card is not read more than once when
inserted and removed.
- Floor Button Monitor:
Whether or not other
call buttons are to be disabled when a floor is
selected
(requires call-button-reporting wiring
between the elevator unit and our floor relay board)
.
- Floor Button Enabled Time:
This is the
duration that the allowed floor call-buttons will
be available after a valid card is presented at the
reader in the elevator (lift) cab.
- Tamper Circuit:
The type of circuit/wiring
associated with the reader tamper
input/sensor. ("Not Required" means this
connection is not being used/monitored.)
Reader
(Elevator (Lift) Reader Settings)
- In Area:
This is the area associated with this
elevator cab.
Time and attendance reporting requires that all
readers used to exit from the "required attendance
zone" be set as "Outside".
This will typically pertain to the interior readers on the
perimeter of the facility, and may also include
additional readers (such as that allow entry to a
cafeteria or fitness room).
Elevator Area: It is best to set up unique area(s) for
use with elevators and the associated access
hallways. This allows the authority to control elevators
and floors to be separated from other features, and
also helps to identify activity/alarm messages
pertaining to elevator readers. (The authority to
control elevators and floors pertains to the "Door
Control" authority selection for the specific area.)
To create a new area, and set up its operating
characteristics, refer to "Areas and Related Settings".
For details on user authorities, refer to "Authorities for
Users/Entrants".
Card Mode
- Schedule
, and
In / Out of schedule:
These
settings specify the basic method required to
satisfy the elevator reader—i.e., present
access token and/or enter a PIN at the
keypad. If scheduled, different access
requirements can be selected for when the
schedule is active versus outside of the
chosen schedule.
UID vs. Card Number: The system can be set to
require a full card number instead of the user-ID
number. (Wherever you see "UID", a card number
would have to be entered instead.)
Related Topic: Account-Wide Panel Settings (look for
"
Setup
", and then "
User Logon Mode
").
Card/PIN: "Card or PIN" means "Card-Only, or User-
ID+PIN". With "Card+PIN", the card must be
presented (does not allow UID+PIN).
Manual Disarming: For an armed area that is NOT set
to 'Auto Disarm on Valid Token', the user will also
have to access the alarm system and disarm the area.
For details on the "Auto-Disarm" feature, refer to
"Areas and Related Settings".